ACSR(Aluminum Conductor Steel Reinforced) is widely used in the overhead power distribution system of our country.
We can supply this conductor according to different recognized standards,such as IEC61089,BS215,ASTM B232,CSA C49,DIN48204,JIS C3110, customer special specification also can be satisfied.
The data sheets below show the most common standards,British standard.
British Sizes BS215
Code name |
Nominal |
Stranding&Wire Diameter |
Approx Overall |
Sectional Area |
Approx |
Breaking Load |
DC Resistance |
Area |
Al |
Steel |
Diameter |
Al |
Steel |
Total |
Weight |
mm 2 |
mm |
mm |
mm |
mm 2 |
mm 2 |
mm 2 |
Kg/km |
KN |
Ohm/km |
Squirrel |
20 |
6/2.11 |
1/2.11 |
6.33 |
21 |
3.5 |
24.5 |
84.7 |
7.87 |
1.3659 |
Gopher |
25 |
6/2.36 |
1/2.36 |
7.08 |
26.24 |
4.38 |
30.62 |
106 |
9.61 |
1.093 |
Ferret |
40 |
6/3.00 |
1/3.00 |
9 |
42.41 |
7.07 |
49.48 |
172 |
15.2 |
0.6766 |
Rabbit |
50 |
6/3.35 |
1/3.35 |
10.05 |
52.88 |
8.82 |
61.7 |
214 |
18.35 |
0.5426 |
Mink |
60 |
6/3.66 |
1/3.66 |
11 |
63.1 |
10.5 |
73.6 |
254.9 |
21.67 |
0.454 |
Horse |
70 |
12/2.79 |
7/2.79 |
13.95 |
73.37 |
42.83 |
116.2 |
538 |
61.2 |
0.3936 |
Dog |
100 |
6/4.72 |
7/1.57 |
14.15 |
105 |
13.5 |
118.5 |
394 |
32.7 |
0.2733 |
Wolf |
150 |
30/2.59 |
7/2.59 |
18.13 |
158.1 |
36.8 |
194.9 |
726 |
69.2 |
0.1828 |
Goat |
300 |
7/3.71 |
7/3.71 |
26 |
324.3 |
75.7 |
400 |
1488.2 |
135.13 |
0.0891 |
Bison |
350 |
7/3.00 |
7/3.00 |
27 |
381.7 |
49.5 |
431.2 |
1442.5 |
121.3 |
0.0758 |
Zebra |
400 |
54/3.18 |
7/3.18 |
28.62 |
428.9 |
55.6 |
484.5 |
1621 |
131.9 |
0.0674 |